品牌:西门子
起订:1个
供应:1000个
发货:3天内
信息标签:西门子6SL3201-0BE12-0AA0,供应,电子、电工,工控系统及装备
Braking resistor for blocksize format, frame sizes FSA and FSC
The PM340 Power Modules cannot regenerate into the line supply. For regenerative operation, e.g. the braking of a rotating mass, a braking resistor must be connected to convert the resulting energy into heat.
The braking resistor is connected at terminals DCP/R1 and R2.
The braking resistors can be installed at the side next to the PM340 Power Modules. The braking resistors for the FSA and FSB frame sizes are designed as base components. If the PM340 Power Modules of the FSA or FSB frame size are operated without line reactor, the braking resistors can also be installed under the Power Modules.
The braking resistors for the Power Modules of the FSC to FSF frame sizes should be placed outside the control cabinet or the switchgear room in order to lead the resulting heat loss away from the Power Modules. The level of air conditioning required is therefore reduced.
The braking resistors are designed with a temperature switch. The temperature switch must be evaluated to prevent consequential damage if the braking resistor overheats.
DC link voltage 240 … 360 V DC |
Braking resistor |
---|---|
6SE6400-4BC05-0AA0 |
|
Resistance |
180 Ω |
Rated power PDB (Continuous braking power) |
0.05 kW |
Peak power Pmax |
1 kW |
Degree of protection 1) |
IP20 |
Power connections |
3 × 1.5 mm2 (shielded) |
|
0.5 m (1.64 ft) |
Thermostatic switch (NC contact) |
|
|
250 V AC/max. 2.5 A |
|
0.5 … 2.5 mm2 |
Dimensions |
|
|
72 mm (2.83 in) |
|
230 mm (9.06 in) |
|
43.5 mm (1.71 in) |
Weight, approx. |
1 kg (2.21 lb) |
Approvals, according to |
cURus |
Suitable for Power Module in blocksize format |
frame size FSA |
1) With correctly connected load connection cable.
DC link voltage 510 V … 720 V DC |
Braking resistor |
||||||
---|---|---|---|---|---|---|---|
6SE6400-4BD11-0AA0 |
6SL3201-0BE12-0AA0 |
6SE6400-4BD16-5CA0 |
6SE6400-4BD21-2DA0 |
6SE6400-4BD22-2EA1 |
6SE6400-4BD24-0FA0 |
||
Resistance |
Ω |
390 |
160 |
56 |
27 |
15 |
8.2 |
Rated powerPDB (Continuous braking power) |
kW |
0.1 |
0.2 |
0.65 |
1.2 |
2.2 |
4 |
Peak powerPmax |
kW |
1.7 |
4.1 |
12 |
24 |
44 |
80 |
Degree of protection 1) |
IP20 |
IP20 |
IP20 |
IP20 |
IP20 |
IP20 |
|
Power connections |
3 × 1.5 mm2(shielded) |
3 × 1.5 mm2(shielded) |
3 × 1.5 mm2(shielded) |
M6 screw stud |
M6 screw stud |
M6 screw stud |
|
|
m (ft) |
0.5 (1.64) |
0.5 (1.64) |
0.9 (2.95) |
– |
– |
– |
Thermostatic switch (NC contact) |
|||||||
|
250 V AC/ |
250 V AC/ |
250 V AC/ |
250 V AC/ |
250 V AC/ |
250 V AC/ |
|
|
mm2 |
0.5 … 2.5 |
0.5 … 2.5 |
0.5 … 2.5 |
0.5 … 2.5 |
0.5 … 2.5 |
0.5 … 2.5 |
Dimensions |
|||||||
|
mm (in) |
72 (2.83) |
153 (6.02) |
185 (7.28) |
270 (10.63) |
301 (11.85) |
400 (15.75) |
|
mm (in) |
230 (9.06) |
329 (12.95) |
285 (11.22) |
515 (20.28) |
483 (19.02) |
650 (25.59) |
|
mm (in) |
43.5 (1.71) |
43.5 (1.71) |
150 (492.15) |
175 (6.89) |
326 (12.83) |
315 (12.4) |
Weight, approx. |
kg (lb) |
1 (2.21) |
1.6 (3.53) |
3.8 (8.38) |
7.4 (16.3) |
10.6 (23.4) |
16.7 (36.8) |
Approvals, according to |
cURus |
cURus |
cURus |
cURus |
cURus |
cURus |
|
Suitable for Power Module in blocksize format |
frame size |
FSA |
FSB |
FSC |
FSD |
FSE |
FSF |
1) With correctly connected load connection cable.
Load diagram for braking resistors in blocksize format